Post

EPLAN Device Designation Reference Guide — Comprehensive `-` Tag System for All Disciplines

A complete reference for EPLAN device designations based on IEC 81346, covering every device type across electrical, automation, instrumentation, IT, and mechanical disciplines, with examples and best practices.

EPLAN Device Designation Reference Guide — Comprehensive `-` Tag System for All Disciplines

EPLAN P8 — Device Designation (-) Reference Guide

Based on IEC 81346IEC 61346ISO 10628ISA-5.1Expert conventions across electrical, automation, instrumentation, IT, and mechanical disciplines

34 sections covering every device type across all disciplines:

Foundation:

  • Full IEC 81346 primary letter table (A–Y) with two-letter combinations and typical devices
  • IEC vs ISA vs common practice cross-reference table — so you know which standard applies when

Power & Protection:

  • LV breakers (QF, MCB, MCCB, ACB, RCBO) with descriptive suffixes for every feeder type
  • MV switching (QB, QD, QS, QE, FU) + VCB-specific (CLOSING_COIL, TRIP_COIL1/2, ANTI_PUMP_K, SPRING_CHARGED, draw-out interlock switches)
  • Protection relays — all types (F_OC, F_EF, F_DIFF, F_DIST, F_REF, F_BUCHH, F_WTI, F_ARC)
  • CTs, VTs, power analysers, energy meters, phase monitors

Motor Control:

  • Contactors — every type (KM_MAIN, KM_STAR, KM_DELTA, KM_FWD, KM_REV, KM_VFD, KM_BP, KM_NORM, KM_ALT)
  • Relays, timers (KT_SD, KT_ON, KT_OFF, KT_RETRANS, KT_FLASH)
  • VFDs, soft starters, braking resistors

Instrumentation (both worlds):

  • IEC BT, BP, BF, BL, BA sensor codes
  • Full ISA-5.1 tag system — first letter table, last letter table, and every common tag (FT101, PT201, TT301, LT401, AT501) with H/L/HH/LL safety suffix convention

PLC & Safety:

  • Every PLC module type (CPU_A/B, PM, IM, DI01, DO01, AI01, RTD01, CM_PN, CM_PB, SYNC_MOD)
  • Safety relays and devices (F3_ESTOP, F3_GUARD, F3_LIGHT, RFID_SAFE, AREA_SCAN, LIGHT_CRT)
  • SIS modules (CPU_S_A/B/C, DI_S01, DO_S01)

Complete worked examples — DOL starter, star-delta, PLC panel, DCS instrumentation loop, MV feeder panel, SIL2 safety shutdown loop (all six showing full =FUNCTION+LOCATION-DEVICE tags)


Table of Contents

  1. Fundamentals
  2. IEC 81346 Device Reference Designation — Letter Codes
  3. Power Devices — Breakers, Isolators, Switches
  4. Protection & Measuring Devices
  5. Contactors, Relays & Timers
  6. Transformers & Power Conversion
  7. Drives, Starters & Motor Control
  8. Motors, Actuators & Prime Movers
  9. Power Supplies & Energy Storage
  10. Terminals, Connectors & Cabling
  11. Sensors & Detectors (Digital / Binary)
  12. Instrumentation — Analog Measurement
  13. Instrumentation — ISA Tag Naming (P&ID)
  14. Control & Signal Conditioning Devices
  15. Indication & Signalling Devices
  16. Operator Interface Devices (Buttons, Switches, Selectors)
  17. PLC & Controller Modules
  18. Safety Devices & Safety Relays
  19. Communications & Network Devices
  20. HMI, Computers & IT Hardware
  21. Heating, Cooling & Environmental
  22. Pneumatic & Hydraulic Devices
  23. Mechanical & Structural Components
  24. Cables, Conduits & Routing
  25. Panel Building Hardware
  26. MV Switchgear Specific Devices
  27. Battery & DC System Devices
  28. Fire, Gas & Safety Detectors
  29. Building Services Devices
  30. Numbering Conventions & Suffixes
  31. Full Tag Examples — Complete Projects
  32. Cross-Reference: IEC 81346 vs ISA-5.1 vs Common Practice
  33. Common Mistakes
  34. Expert Tips

Fundamentals

The Three Pillars of EPLAN Referencing (IEC 81346)

1
2
3
=   Function designation     → WHAT it does
+   Location designation     → WHERE it is
-   Device designation       → WHAT it is (the component itself)

What Device Designation Represents

The - designation is the tag of the actual component — it uniquely identifies the physical device within its location and function context. It answers:

“Which specific component is this?”

Full Tag Syntax

1
2
3
4
5
6
=FUNCTION+LOCATION-DEVICE

=CTRL+CP1-CPU1             PLC CPU, in panel CP1, control function
=PWR+MCC1.M01-KM1          Contactor KM1, in MCC drawer M01, power function
=INST+FIELD-FT101          Flow transmitter FT101, in field, instrumentation
=SAFE+CP1.SAFE-F3_ESTOP    Safety relay, in safety section of CP1

Numbering Structure

1
2
3
4
5
6
7
8
9
10
11
12
[Letter Code] + [Number]          Basic form
[Letter Code] + [Number] + [Suffix]   Extended form

Examples:
-K1            Relay 1
-KM1           Main contactor 1
-KM_STAR       Star contactor (named suffix)
-F1            Protection device 1
-F_OC_A        Overcurrent relay, incomer A (descriptive suffix)
-QF1           Circuit breaker 1 (Q = switching, F = protection)
-PQ1           Power quality analyser 1
-FT101         Flow transmitter tag 101 (ISA style)

When to Use Numbers vs Descriptive Suffixes

1
2
3
4
5
6
7
8
9
10
11
12
13
14
Numbers alone (recommended for simple panels):
-K1, -K2, -K3          Easy, sequential, no ambiguity

Descriptive suffixes (recommended for complex panels):
-KM_MAIN               Immediately clear this is the main contactor
-KM_STAR               Star contactor in star-delta
-KM_DELTA              Delta contactor in star-delta
-K_WD                  Watchdog relay
-F_OC                  Overcurrent protection

ISA instrument tags (process / P&ID projects):
-FT101                 Flow transmitter loop 101
-PT302                 Pressure transmitter loop 302
-TIC401                Temperature indicating controller loop 401

IEC 81346 Device Reference Designation — Letter Codes

The first letter(s) define the device type. IEC 81346 uses a two-level system.

Primary Letter — Device Kind

| Letter | Device Kind | Typical Devices | |——–|————|—————-| | B | Converts physical variable → signal | Sensors, transducers, encoders, detectors | | C | Stores energy or material | Capacitors, batteries, tanks, accumulators | | D | Processes / stores information | PLCs, computers, HMIs, recorders, displays | | E | Provides radiation or thermal energy | Heaters, lamps, UV emitters | | F | Protects against dangerous conditions | Fuses, breakers, protection relays, safety devices | | G | Generates / supplies electrical energy | Power supplies, batteries, generators, UPS | | H | Signals / indicates state or condition | Lamps, buzzers, horns, displays, annunciators | | K | Processes signals / controls / switches | Relays, timers, contactors, PLC outputs | | M | Provides mechanical energy | Motors, actuators, cylinders, pumps (motor part) | | N | Regulates / controls process variable | VFDs, PID controllers, regulators | | P | Measures / tests | Meters, analysers, instruments, gauges | | Q | Switches / varies electrical energy | Isolators, circuit breakers, disconnectors | | R | Restricts / stabilises energy or flow | Resistors, reactors, chokes, dampers | | S | Converts manual operation → signal | Push buttons, switches, selectors, keyboards | | T | Converts electrical quantities | Transformers, CT, VT, rectifiers, inverters | | U | Keeps objects in a defined position | Clamps, brakes, locks, holders | | V | Processes materials or products | Conveyors, mixers, reactors, valves (flow) | | W | Conducts / transmits / distributes | Cables, busbars, waveguides, antenna | | X | Connects / terminates | Terminal blocks, connectors, plugs, junction | | Y | Positions / guides | Positioners, guides, stepper actuators |

Common Two-Letter Combinations Used in Practice

| Code | Meaning | Example Device | |——|———|—————-| | BK | Encoder / speed sensor | Rotary encoder | | BP | Pressure sensor | Pressure switch | | BT | Temperature sensor | Thermocouple, PT100 | | BL | Level sensor | Float switch, level switch | | BF | Flow sensor | Flow switch | | BA | Analyser sensor | Gas analyser input | | BG | Position / limit switch | Proximity sensor, limit switch | | CM | Motor capacitor | Run / start capacitor | | DD | Data / logic processor | PLC, computer | | EH | Heating element | Trace heating, panel heater | | EL | Lighting element | Lamp, LED strip | | FA | Fuse (general) | Cartridge fuse | | FB | Overcurrent protective device | MCCB, MCB | | FC | Combined protective device | RCBO, motor circuit breaker | | FD | Residual current device | RCD, RCCB | | FU | HV fuse | HRC fuse, expulsion fuse | | GA | Battery | Lead-acid, Li-ion battery | | GB | Battery charger | Float charger, SMPS charger | | GS | Power supply (AC/DC) | SMPS, linear PSU | | GU | UPS | UPS system | | HA | Acoustic alarm | Buzzer, horn, siren | | HL | Indicator lamp | Pilot lamp, LED indicator | | HR | Digital display / readout | Digital panel meter | | KA | Auxiliary relay | General purpose relay | | KC | Contactor | Motor contactor | | KM | Main contactor | Main power contactor | | KT | Timer relay | On-delay, off-delay, star-delta timer | | KW | Watchdog relay | PLC watchdog output | | MA | Motor (asynchronous) | AC induction motor | | MB | Brake (motor) | Electro-mechanical brake | | MC | Motor (DC) | DC motor | | MS | Servo motor | Servo / stepper motor | | MT | Motor (special) | Torque motor, linear motor | | NA | VFD / frequency converter | Variable frequency drive | | NC | PID controller | Process controller | | NR | Regulator | Voltage regulator, pressure regulator | | PA | Ammeter | Current meter | | PB | Power analyser | Power quality analyser | | PC | Counter | Event counter, hour meter | | PF | Frequency meter | Hz meter | | PH | Phase sequence relay | Phase monitor relay | | PJ | Energy meter | kWh meter | | PQ | Power quality analyser | PQ meter with harmonics | | PV | Voltmeter | Voltage panel meter | | PW | Power meter | kW meter | | QA | Switch / disconnector | Load break switch, isolator | | QB | Circuit breaker (HV) | Vacuum/SF6 circuit breaker | | QD | Disconnector / isolator (HV) | Air-break disconnector | | QE | Earthing switch | Earth switch (MV/HV) | | QF | Circuit breaker (LV) | MCCB, MCB, ACB | | QM | Motor circuit breaker | Combined contactor + breaker | | QS | Load break switch | LBS, on-load switch | | RA | Resistor | Fixed resistor | | RB | Braking resistor | Dynamic brake resistor | | RL | Inductor / reactor | Line reactor, choke | | RR | Variable resistor | Rheostat, potentiometer | | SA | Selector switch | Multi-position rotary switch | | SB | Push button | Momentary push button | | SK | Key switch | Key-operated switch | | SL | Limit switch (manual) | Mechanical limit switch | | SS | Selector switch (maintained) | Mode selector, local/remote | | TA | Current transformer | Metering / protection CT | | TC | Thyristor / SCR | Power thyristor, soft starter | | TF | Filter transformer | Isolation transformer | | TM | Power transformer | Distribution transformer | | TV | Voltage transformer | Metering / protection VT/PT | | TY | Rectifier / converter | AC/DC converter | | VA | Valve (process) | Control valve, on/off valve | | VF | Fan | Cooling fan, ventilation fan | | VP | Pump | Process pump | | XB | Busbar | Busbar connection point | | XD | Distribution terminal | DIN rail terminal block | | XP | Plug / socket | Connector plug | | XS | Socket | Socket outlet | | XT | Terminal block | Screw/spring terminal | | YA | Solenoid actuator | Solenoid coil, solenoid valve | | YB | Brake | Electromechanical brake | | YV | Solenoid valve | Pneumatic / hydraulic solenoid valve | | ZA | Zener barrier | Intrinsic safety barrier | | ZI | Galvanic isolator | HART isolator, signal isolator | | ZF | EMC filter | Line filter, EMC filter |


Power Devices — Breakers, Isolators, Switches

LV Circuit Breakers & Isolators

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
-QF_MAIN           Main incomer air circuit breaker (ACB) — mains level
-QF_INC            Incomer MCCB (moulded case circuit breaker)
-QF1 .. -QFn       Numbered outgoing circuit breakers / MCBs
-QF_MCC1           Feeder breaker to MCC1
-QF_DB1            Feeder breaker to DB1
-QF_UPS            Feeder breaker to UPS
-QF_PLC            MCB for PLC power
-QF_HMI            MCB for HMI power
-QF_FIELD          MCB for field device power
-QF_SAFE           MCB for safety system power
-QF_HEAT           MCB for panel heater
-QF_LIGHT          MCB for panel lighting
-QF_24V            MCB for 24VDC supply
-QS1 .. -QSn       Load break switch / isolator (maintained open/close)
-QS_LOCAL          Local isolator switch
-QS_MBP            Maintenance bypass switch (UPS)
-QR1               Residual current circuit breaker (RCCB)
-RCBO1             RCBO (RCD + MCB combined)
-MCB_L1            MCB for lighting circuit 1
-MCB_P1            MCB for power circuit 1
-MCB_H1            MCB for HVAC circuit 1
-MCB_E1            MCB for emergency circuit

HV / MV Switching Devices

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
-QB1 .. -QBn       Vacuum / SF6 circuit breaker (HV/MV)
-QB_INC            Incomer VCB
-QB_TIE            Bus tie / bus section VCB
-QB_FDR1           Feeder VCB 1
-QB_TX1            Transformer feeder VCB
-QB_MTR1           MV motor feeder VCB
-QD1 .. -QDn       Disconnector / isolator (air-break, HV)
-QD_LINE           Line side disconnector
-QD_BUS            Bus side disconnector
-QS1 .. -QSn       Load break switch (MV — ring main, RMU)
-QS_RING_IN        Ring incomer LBS
-QS_RING_OUT       Ring outgoing LBS
-QS_TX             TX feeder LBS
-QE1 .. -QEn       Earthing switch (MV/HV)
-ES1 .. -ESn       Earthing switch (alternative common naming)
-ES_LINE           Line earth switch
-ES_BUS            Busbar earth switch
-FU1 .. -FUn       HRC fuse (MV transformer feeder)

Manual Isolation & Changeover

1
2
3
4
5
6
7
8
-QS_MAINS          Mains isolation switch
-QS_GEN            Generator isolation switch
-QS_ATS            ATS changeover switch (manual)
-QS_NORM           Normal supply isolator
-QS_ALT            Alternative supply isolator
-COS1              Changeover switch (manual 2-position)
-MTS1              Manual transfer switch
-ISOL1             Panel isolation switch (lockable)

Protection & Measuring Devices

Protection Relays

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-F1 .. -Fn         General protection device (numbered)
-F_OC              Overcurrent protection relay
-F_EF              Earth fault protection relay
-F_DIFF            Differential protection relay
-F_DIST            Distance protection relay
-F_REF             Restricted earth fault relay
-F_BUCHH           Buchholz relay (oil transformer)
-F_WTI             Winding temperature indicator / relay
-F_OTI             Oil temperature indicator / relay
-F_PRD             Pressure relief device / relay
-F_OSL             Oil surge relay / gas relay
-F_UV              Undervoltage relay
-F_OV              Overvoltage relay
-F_PHASE           Phase sequence / phase loss relay
-F_MOTOR           Motor protection relay (multifunction)
-F_THERM           Thermal overload relay (standalone)
-F_SAFE            Safety relay (non-SIL general purpose)
-F_BUSBAR          Busbar protection relay
-F_ARC             Arc flash detection relay
-F_FREQ            Under/over frequency relay

Measurement & Metering

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
-CT1 .. -CTn       Current transformer (protection / metering)
-CT_INC            Incomer CT
-CT_FDR1           Feeder CT 1
-VT1 .. -VTn       Voltage transformer / potential transformer
-VT_BUS            Busbar VT
-VT_METER          Metering VT
-PA1               Ammeter (panel-mount)
-PV1               Voltmeter (panel-mount)
-PW1               Wattmeter / power meter
-PF1               Power factor meter
-PQ1 .. -PQn       Power quality analyser (full PQ with harmonics)
-PQ_MAIN           Main incomer power quality analyser
-PQ_FDR1           Feeder 1 power quality analyser
-KWH1 .. -KWHn     Energy meter / kWh meter
-KWH_MAIN          Main energy meter
-KWH_LIGHT         Lighting sub-meter
-KWH_POWER         Power sub-meter
-FREQ1             Frequency meter
-PH1               Phase sequence indicator
-PC1               Hour meter / event counter
-PLC_METR1         Power line carrier meter
-THD1              Total harmonic distortion analyser

Contactors, Relays & Timers

Contactors

1
2
3
4
5
6
7
8
9
10
11
12
13
-KM1 .. -KMn       Main contactor (general numbered)
-KM_MAIN           Main power contactor (DOL starter)
-KM_STAR           Star contactor (star-delta starter)
-KM_DELTA          Delta contactor (star-delta starter)
-KM_FWD            Forward contactor (reversing starter)
-KM_REV            Reverse contactor (reversing starter)
-KM_VFD            VFD output contactor
-KM_BP             Bypass contactor (VFD bypass)
-KM_RUN            Run bypass contactor (soft starter inline type)
-KM_NORM           Normal supply contactor (ATS)
-KM_ALT            Alternative supply contactor (ATS)
-KM_COOL           Cooling fan contactor (transformer)
-KM_AUX            Auxiliary contactor (signal/interlock duty)

Auxiliary & Interposing Relays

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
-K1 .. -Kn         General relay (numbered)
-KA1 .. -KAn       Auxiliary relay (IEC 81346 style)
-K_START           Start permissive relay
-K_STOP            Stop command relay
-K_RUN             Running confirm relay
-K_TRIP            Trip / fault relay
-K_FAULT           General fault relay
-K_ALARM           General alarm relay
-K_READY           Ready / healthy relay
-K_REMOTE          Remote command relay
-K_LOCAL           Local command relay
-K_ATS             ATS changeover relay
-K_INC_A           Incomer A auxiliary relay
-K_TIE             Bus tie interlock relay
-K_WD              Watchdog relay (PLC healthy)
-K_INTERLOCK       Interlock relay (general)
-K_PERMISSIVE      Permissive relay
-K_INHIBIT         Inhibit relay
-K_LATCH           Latching relay
-KP1               Pulse relay
-KR1               Reed relay
-KM_AUX1           Auxiliary contact block (add-on)

Timers

1
2
3
4
5
6
7
8
9
10
-KT1 .. -KTn       Timer relay (general numbered)
-KT_SD             Star-delta changeover timer
-KT_ON             On-delay timer
-KT_OFF            Off-delay timer
-KT_RETRANS        Retransfer delay timer (ATS)
-KT_TRANS          Transfer delay timer (ATS)
-KT_START          Start delay timer
-KT_RESTART        Auto-restart delay timer
-KT_FLASH          Flasher / pulse timer
-KT_WD             Watchdog timer

Transformers & Power Conversion

Power Transformers

1
2
3
4
5
6
7
8
-TM1 .. -TMn       Power transformer (general)
-TM_MAIN           Main power transformer
-TX1 .. -TXn       Transformer (alternative common tag)
-T1 .. -Tn         Transformer (simple projects)
-T_CTRL            Control transformer (230V to 24VAC)
-T_ISO             Isolation transformer
-T_AUTO            Autotransformer
-TF1               Filter / EMC transformer

Instrument Transformers

1
2
3
4
-CT1 .. -CTn       Current transformer
-VT1 .. -VTn       Voltage transformer (potential transformer)
-TA1               Current transformer (IEC 81346 two-letter)
-TV1               Voltage transformer (IEC 81346 two-letter)

Power Conversion

1
2
3
4
5
6
-TY1               Rectifier / AC-DC converter
-INV1              Inverter (DC-AC)
-CONV1             Converter (general)
-TC1               Thyristor controller / soft starter power stack
-CHRG1             Battery charger
-GB1               Battery charger (IEC 81346 style)

Reactors & Filters

1
2
3
4
5
6
7
8
-RL1 .. -RLn       Line reactor / choke (VFD, harmonic)
-L1                Inductor (simple notation)
-EMC1 .. -EMCn     EMC line filter
-ZF1               EMC filter (IEC 81346 style)
-THF1              Tuned harmonic filter
-HF1               High-frequency filter
-C1 .. -Cn         Capacitor (power factor / filter)
-CM1               Motor run capacitor

Drives, Starters & Motor Control

Variable Frequency Drives (VFDs)

1
2
3
4
5
6
7
8
9
-VFD1 .. -VFDn     VFD unit (general numbered)
-VFD_X             VFD for X-axis
-VFD_Y             VFD for Y-axis
-VFD_Z             VFD for Z-axis
-VFD_SP            VFD for spindle
-VFD_P1            VFD for pump 1
-VFD_FAN1          VFD for fan 1
-NA1 .. -NAn       VFD / frequency converter (IEC 81346 two-letter)
-INV_MAIN          Main drive inverter

Soft Starters

1
2
3
-SS1 .. -SSn       Soft starter unit (general numbered)
-SS_P1             Soft starter for pump 1
-TC1 .. -TCn       Thyristor controller / soft starter (IEC 81346)

Motor Protection & Starter Components

1
2
3
4
5
6
7
-F_THERM1          Thermal overload relay
-F_MOTOR1          Motor protection relay (multifunction — Siemens 3RU, ABB EF, Sprecher)
-QM1               Motor circuit breaker (combined QF + thermal protection)
-KM_MAIN           Main contactor
-KM_AUX            Auxiliary contact block
-PTC1              PTC thermistor trip relay (winding temperature)
-NTC1              NTC temperature monitoring relay

Braking

1
2
3
4
5
-RB1 .. -RBn       Braking resistor (dynamic brake for VFD)
-BR1               Brake resistor (alternative notation)
-YB1               Electromechanical brake (motor-mounted)
-MB1               Brake (IEC 81346 two-letter)
-BC1               Brake controller / rectifier

Motors, Actuators & Prime Movers

Motors

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
-M1 .. -Mn         Motor (general numbered — most common)
-MA1 .. -MAn       AC induction motor (IEC 81346 two-letter)
-MC1               DC motor
-MS1               Servo motor
-MT1               Torque motor / special motor
-P1 .. -Pn         Pump motor (process / P&ID convention — see ISA section)
-FAN1 .. -FANn     Fan motor (common in HVAC)
-COMP1             Compressor motor
-CONV1             Conveyor drive motor
-SP1               Spindle motor
-AG1               Agitator motor
-MIX1              Mixer motor
-BLW1              Blower motor
-PUMP1             Pump motor (descriptive)
-HYD_MTR1          Hydraulic power unit motor
-EXT1              Extruder motor

Actuators & Valves

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
-YA1 .. -YAn       Solenoid actuator / solenoid valve coil
-YV1 .. -YVn       Solenoid valve (pneumatic / hydraulic)
-YV_FWD            Forward solenoid valve
-YV_REV            Reverse solenoid valve
-YV_CLAMP          Clamp solenoid valve
-YV_UNCLAMP        Unclamp solenoid valve
-VA1               Control valve (process — motorised)
-VA_CTRL1          Control valve positioner
-MOV1              Motor-operated valve
-AOV1              Air-operated valve / pneumatic valve
-HOV1              Hand-operated valve (if monitored)
-POS1              Valve positioner
-ACT1              Linear actuator (electric)
-ACT_SERVO1        Servo actuator
-CYL1 .. -CYLn     Hydraulic / pneumatic cylinder
-GRAB1             Gripper actuator

Mechanical Drives

1
2
3
4
-GB1               Gearbox (monitored — speed feedback)
-CLUTCH1           Clutch (electric)
-BRAKE1            Mechanical brake (release coil)
-COUPLING1         Flexible coupling (if instrumented)

Power Supplies & Energy Storage

Power Supplies

1
2
3
4
5
6
7
8
9
10
11
-PS1 .. -PSn       Power supply unit (general numbered)
-PS_A              Power supply A (redundant pair)
-PS_B              Power supply B (redundant pair)
-GS1               SMPS / switch-mode power supply (IEC 81346)
-SMPS1             Switch-mode power supply
-PSU1              Power supply unit
-PS_PLC            PLC power supply (system power module)
-PS_IO             I/O power supply
-PS_LOOP1          Loop power supply (4-20mA instrument loops)
-PS_SAFE           Safety system power supply (isolated)
-PM1               Power module (PLC-integrated, e.g. Siemens PM)

UPS & Buffering

1
2
3
4
5
-UPS1 .. -UPSn     UPS unit
-GU1               UPS (IEC 81346 two-letter)
-UPS_BUF1          24VDC UPS buffer module (DIN rail, e.g. SITOP UPS1600)
-BATT_BUF1         Battery buffer module
-BATT_MGT1         Battery management module

Batteries & Capacitors

1
2
3
4
5
-GA1 .. -GAn       Battery / battery bank
-BATT1             Battery (common industrial notation)
-C1 .. -Cn         Capacitor (power / filter)
-CAP1              Supercapacitor module
-CB1               Capacitor bank (PFC step)

Terminals, Connectors & Cabling

Terminal Blocks

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
-X1 .. -Xn         Terminal block / terminal strip (general — most common)
-XT1               Terminal block (IEC 81346 two-letter)
-X_DI1             Digital input terminal group
-X_DO1             Digital output terminal group
-X_AI1             Analog input terminal group
-X_AO1             Analog output terminal group
-X_RTD1            RTD input terminal group
-X_SAFE1           Safety circuit terminal group
-X_PWR1            Power terminal group
-X_COMM1           Communications terminal group
-X_EARTH           Earth / PE terminal bar
-X_SCREEN          Cable screen / shield terminal
-XD1               DIN rail terminal (IEC 81346)
-PE1               Protective earth terminal bar
-N1                Neutral terminal bar

Connectors & Plugs

1
2
3
4
5
6
7
8
9
10
-XP1 .. -XPn       Plug / male connector
-XS1 .. -XSn       Socket / female connector
-XP_PWR            Power connector plug
-XP_COMM           Communications connector (M12, RJ45 on device)
-XP_HMI            HMI connection plug
-XP_USB            USB connector
-XP_SD             SD card / memory card
-XB1               Busbar connector (IEC 81346)
-JB1               Junction block (multi-pin)
-MC1               Multi-pin connector (general)

Cable & Wiring References

1
2
3
4
5
6
7
8
9
10
-W1 .. -Wn         Cable / wire (IEC 81346 — W = conducting)
-WC1               Control cable
-WP1               Power cable
-WS1               Signal cable
-WF1               Fibre optic cable
-WN1               Network cable (Cat6, etc.)
-CAB1              Cable (common industrial notation)
-PIGTAIL1          Fibre pigtail
-JUMPER1           Jumper wire / patch lead
-LOOM1             Wire loom / harness

Sensors & Detectors (Digital / Binary)

Position & Presence

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
-B1 .. -Bn         Sensor / detector (general — most common simple notation)
-BG1 .. -BGn       Position / limit sensor (IEC 81346)
-SL1 .. -SLn       Mechanical limit switch
-SQ1 .. -SQn       Proximity / position switch (common European notation)
-BQ1               Proximity switch (IEC 81346)
-PROX1             Inductive proximity sensor
-PROX_EXT1         Extended range proximity sensor
-CAP1              Capacitive proximity sensor
-ULTRA1            Ultrasonic proximity sensor
-PHOTO1            Photoelectric sensor
-REFLX1            Retro-reflective photosensor
-THR_BEAM1         Through-beam sensor
-LASER1            Laser distance / presence sensor
-COLOUR1           Colour sensor
-RFID1             RFID reader
-LS1               Level switch (discrete — float or electrode)
-FS1               Flow switch (discrete — paddle or thermal)
-PS_SW1            Pressure switch (discrete)
-TS_SW1            Temperature switch (discrete — bimetal or capillary)
-VS1               Vibration switch
-TILT1             Tilt switch
-SLIP1             Slip detection sensor
-ROPE_SW1          Rope / cable pull switch (conveyor safety)
-SKIRT1            Skirt monitoring switch
-BELT_ALIGN1       Belt alignment switch
-ZERO_SPD1         Zero speed switch
-OVERSPD1          Overspeed switch / detector

Door, Guard & Safety Sensing

1
2
3
4
5
6
7
-SL_DOOR1          Door limit switch
-SL_GUARD1         Guard door limit switch
-SL_HATCH1         Hatch / access panel switch
-MAG_SW1           Magnetic door switch
-RFID_GUARD1       RFID guard lock / interlock
-TPSW1             Trapped key switch
-HANDLE1           Handle switch

Rotational & Motion

1
2
3
4
5
6
7
-BK1 .. -BKn       Encoder (IEC 81346)
-ENC1              Rotary encoder (absolute or incremental)
-ENC_ABS1          Absolute encoder
-ENC_INC1          Incremental encoder
-RESOLVER1         Resolver feedback
-TACHO1            Tachometer (analogue speed feedback)
-SPEED1            Speed sensor (magnetic pickup)

Instrumentation — Analog Measurement

Temperature

1
2
3
4
5
6
7
8
9
-BT1 .. -BTn       Temperature sensor (IEC 81346)
-TT1 .. -TTn       Temperature transmitter (ISA style — 4-20mA output)
-TE1 .. -TEn       Temperature element (thermocouple or RTD — ISA)
-RTD1              RTD sensor (PT100/PT1000 — direct)
-TC_THERMO1        Thermocouple element (K, J, T type)
-TW1               Thermowell (protective pocket for TE)
-TSTAT1            Thermostat (discrete control — see also SB / SS)
-WT1               Winding temperature sensor (transformer)
-OT1               Oil temperature sensor (transformer)

Pressure

1
2
3
4
5
6
-BP1 .. -BPn       Pressure sensor (IEC 81346)
-PT1 .. -PTn       Pressure transmitter (ISA style)
-PE1 .. -PEn       Pressure element (ISA)
-PDT1              Pressure differential transmitter
-PG1               Pressure gauge (local — no signal output)
-PSV1              Pressure safety valve (relief — not a sensor but appears on I/O)

Flow

1
2
3
4
5
6
7
8
9
10
11
-BF1 .. -BFn       Flow sensor (IEC 81346)
-FT1 .. -FTn       Flow transmitter (ISA style)
-FE1 .. -FEn       Flow element (orifice plate, venturi — ISA)
-FIT1              Flow indicating transmitter
-FC1               Flow controller
-FM1               Flow meter (volumetric, Coriolis, magnetic)
-MAG1              Magnetic flow meter
-CORI1             Coriolis flow meter
-ULTRA_F1          Ultrasonic flow meter
-VORTEX1           Vortex flow meter
-ROTA1             Rotameter / variable area flow meter

Level

1
2
3
4
5
6
7
8
9
10
11
12
-BL1 .. -BLn       Level sensor (IEC 81346)
-LT1 .. -LTn       Level transmitter (ISA style — continuous)
-LE1 .. -LEn       Level element (ISA)
-LIT1              Level indicating transmitter
-LG1               Level gauge / sight glass (local)
-RADAR1            Radar level transmitter (guided wave or free space)
-ULTRA_L1          Ultrasonic level transmitter
-BUBBLER1          Bubbler level system
-DISPL1            Displacer level transmitter
-FLOAT1            Float-type level sensor
-HYDRO1            Hydrostatic level transmitter
-LOAD_CELL1        Load cell (for level by weight)

Analytical

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
-BA1 .. -BAn       Analyser sensor (IEC 81346)
-AT1 .. -ATn       Analytical transmitter (ISA style)
-AE1 .. -AEn       Analytical element (ISA)
-PH_METER1         pH analyser / transmitter
-COND1             Conductivity analyser
-DO2_1             Dissolved oxygen analyser
-TURB1             Turbidity analyser
-CL2_1             Chlorine residual analyser
-TOC1              Total organic carbon analyser
-GAS_IR1           Infrared gas analyser (CO2, CH4, etc.)
-GAS_CATA1         Catalytic gas detector (%LEL)
-GAS_EC1           Electrochemical gas detector (H2S, CO, O2, etc.)
-GAS_OP1           Open-path gas detector (IR beam)
-FLUE1             Flue gas analyser
-MOISTURE1         Moisture / humidity transmitter
-VISCOSITY1        Viscosity analyser

Position & Displacement (Analog)

1
2
3
4
-LVDT1             LVDT position transducer
-POT1              Potentiometer (position feedback)
-LINEAR_ENC1       Linear encoder
-DRAW_WIRE1        Draw-wire / cable extension transducer

Force, Torque & Vibration

1
2
3
4
5
6
-LOAD_CELL1        Load cell (force / weight)
-TORQUE1           Torque transducer
-STRAIN1           Strain gauge transmitter
-VIB_TX1           Vibration transmitter (4-20mA, proximity probe)
-ACCEL1            Accelerometer (vibration / shock)
-BEARING_TX1       Bearing temperature / vibration transmitter

Instrumentation — ISA Tag Naming (P&ID)

ISA-5.1 standard. First letter(s) = measured variable, last letter(s) = function/device type.

First Letter — Measured Variable

| Letter | Variable | |——–|———| | A | Analysis (composition) | | C | Conductivity | | D | Density | | F | Flow | | H | Hand (manual) | | I | Current (electrical) | | J | Power | | K | Time | | L | Level | | M | Moisture / humidity | | P | Pressure | | Q | Quantity / event | | R | Radiation | | S | Speed / frequency | | T | Temperature | | U | Multivariable | | V | Vibration / viscosity | | W | Weight / force | | X | Unclassified | | Y | Event / state (relay) | | Z | Position / dimension |

Last Letter(s) — Function / Device Type

| Letter(s) | Function | |———–|———| | E | Primary element (sensing element, no output) | | T | Transmitter (4-20mA / HART / FF output) | | I | Indicator (local display only) | | C | Controller | | R | Recorder | | S | Switch (discrete output) | | V | Control valve (final control element) | | IT | Indicating transmitter | | IC | Indicating controller | | IR | Indicating recorder | | ICV | Indicating control valve (with positioner) |

Common ISA Tags Used as Device Designations

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
--- Flow ---
-FE101             Flow element (orifice plate) loop 101
-FT101             Flow transmitter loop 101
-FIT101            Flow indicating transmitter
-FS101             Flow switch (discrete)
-FC101             Flow controller
-FCV101            Flow control valve
-FM101             Flow meter (totalisers)

--- Pressure ---
-PE201             Pressure element loop 201
-PT201             Pressure transmitter
-PIT201            Pressure indicating transmitter
-PS201             Pressure switch (discrete)
-PC201             Pressure controller
-PCV201            Pressure control valve
-PSV201            Pressure safety valve
-PDT201            Differential pressure transmitter

--- Temperature ---
-TE301             Temperature element (thermocouple/RTD)
-TT301             Temperature transmitter
-TIT301            Temperature indicating transmitter
-TS301             Temperature switch (discrete)
-TC301             Temperature controller
-TW301             Thermowell

--- Level ---
-LE401             Level element
-LT401             Level transmitter
-LIT401            Level indicating transmitter
-LS401             Level switch (discrete — high or low)
-LSH401            Level switch high
-LSL401            Level switch low
-LSHH401           Level switch high-high (SIL — safety trip)
-LSLL401           Level switch low-low (SIL — safety trip)
-LG401             Level gauge (local — no signal)
-LC401             Level controller
-LCV401            Level control valve

--- Analytical ---
-AE501             Analytical element
-AT501             Analytical transmitter
-AIT501            Analytical indicating transmitter
-AS501             Analytical switch

--- Vibration ---
-VT601             Vibration transmitter
-VS601             Vibration switch
-VIT601            Vibration indicating transmitter

--- Speed ---
-ST701             Speed transmitter
-SS701             Speed switch (discrete — zero speed / overspeed)
-SE701             Speed element (magnetic pickup)

--- Position / Valve Status ---
-ZT801             Position transmitter (valve)
-ZS801             Position switch (limit switch — valve open/closed)
-ZSO801            Position switch — open
-ZSC801            Position switch — closed

--- Multifunction transmitters ---
-UT901             Multivariable transmitter
-TDT1001           Temperature differential transmitter

Control & Signal Conditioning Devices

Isolators & Signal Conditioners

1
2
3
4
5
6
7
8
9
10
11
12
-Z1 .. -Zn         Zener barrier / isolator (general)
-ZA1 .. -ZAn       Zener barrier (intrinsic safety — IEC 81346)
-ZI1 .. -ZIn       Galvanic isolator (IEC 81346)
-ISO1              Galvanic isolator (common notation)
-HART_ISO1         HART-transparent galvanic isolator
-SC1               Signal conditioner (4-20mA repeater / splitter)
-SC_SPLIT1         Signal splitter (1 in → 2 out)
-SC_CONV1          Signal converter (0-10V → 4-20mA, etc.)
-SC_LIMIT1         Signal limiter / trip amplifier
-SC_ALARM1         Alarm trip amplifier
-MTL1              MTL Zener barrier (by brand — common usage)
-P&F1              Pepperl+Fuchs isolator (by brand — common usage)

Loop & Power Conditioning

1
2
3
4
5
-PS_LOOP1          Loop power supply (for 4-20mA sensors)
-SPLITTER1         Power / signal splitter
-REPEATER1         Signal repeater (RS485, etc.)
-CONVERTER1        Protocol converter
-MODEM1            Modem (RS232/485 to TCP/IP, etc.)

Indication & Signalling Devices

Indicator Lamps

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
-HL1 .. -HLn       Indicator lamp / pilot light (general — most common)
-HL_POWER          Power on / system healthy (green)
-HL_RUN            Running / active (green)
-HL_STOP           Stopped / off (white or blue)
-HL_FAULT          Fault / alarm (red)
-HL_WARN           Warning (amber / yellow)
-HL_READY          Ready (green or white)
-HL_TRIP           Trip / protection operated (red)
-HL_CLOSED         Breaker/contactor closed (red — IEC convention)
-HL_OPEN           Breaker/contactor open (green — IEC convention)
-HL_REMOTE         Remote mode active (blue or white)
-HL_LOCAL          Local mode active (amber)
-HL_AUTO           Auto mode active (green)
-HL_MANUAL         Manual mode active (amber)
-HL_ESTOP          E-stop active (red)
-HL_SAFE           Safe / guard active (amber)
-HL_COMM           Communications fault (red)
-HL_BATT           Battery / UPS on battery (amber)
-HL_NORM           Normal supply (green)
-HL_ALT            Alternative supply (amber)
-HL_STAR           Star mode (star-delta — amber)
-HL_DELTA          Delta mode (star-delta — green)

Audible & Visual Alarms

1
2
3
4
5
6
7
8
9
10
11
12
13
14
-HA1 .. -HAn       Audible alarm — buzzer / horn (IEC 81346)
-HORN1             Alarm horn / siren
-BUZZ1             Buzzer
-SIREN1            Siren (multi-tone)
-BELL1             Bell
-BEAC1             Beacon / revolving light
-STACK_LIGHT1      Stack light / signal tower (combined)
-HL_STACK_G        Stack light — green section
-HL_STACK_A        Stack light — amber section
-HL_STACK_R        Stack light — red section
-HL_STACK_B        Stack light — blue section
-ANNUNC1           Annunciator panel / window annunciator
-DISPLAY1          Digital display / alphanumeric readout
-HR1               Panel meter / digital readout (IEC 81346)

Operator Interface Devices (Buttons, Switches, Selectors)

Push Buttons

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
-SB1 .. -SBn       Push button (general — most common)
-SB_START          Start push button (green)
-SB_STOP           Stop push button (red)
-SB_RESET          Fault reset push button (blue or black)
-SB_ACK            Alarm acknowledge push button
-SB_JOG            Jog / inch push button (black)
-SB_FWD            Forward push button
-SB_REV            Reverse push button
-SB_UP             Up push button
-SB_DOWN           Down push button
-SB_OPEN           Open push button (valve / door)
-SB_CLOSE          Close push button (valve / door)
-SB_TEST           Test push button (lamp test)
-SB_LAMP_TEST      Lamp test push button
-SB_ESTOP          Emergency stop (mushroom head, latching red)
-SB_SAFE_RESET     Safety reset push button
-SB_ENABLE         Enable / enable-for-jog push button

Selector & Maintained Switches

1
2
3
4
5
6
7
8
9
-SS1 .. -SSn       Selector switch (general maintained — most common)
-SS_LOCAL          Local / Remote / Off selector
-SS_MODE           Mode selector (Auto / Manual / Maintenance)
-SS_SPEED          Speed selector (Low / Medium / High)
-SA1               Rotary selector switch (IEC 81346)
-SS_3POS           3-position selector (Left / Off / Right)
-SS_HAND_OFF_AUTO  Hand / Off / Auto selector (HOA — common in process)
-SS_VFD_BP         VFD / Bypass selector
-SS_DIR            Direction selector (Forward / Off / Reverse)

Key Switches

1
2
3
4
5
6
-SK1 .. -SKn       Key switch (general)
-SK_MAINT          Maintenance mode key switch
-SK_BYPASS         Safety bypass key switch
-SK_ENABLE         Enable key switch
-SK_MASTER_RESET   Master reset key switch
-TPKS1             Trapped key switch (safety interlock system)

Potentiometers & Analogue Operator Devices

1
2
3
-RR1               Potentiometer / rheostat (speed setpoint)
-SPEED_POT1        Speed reference potentiometer
-SETPOINT1         Analogue setpoint adjuster

Joysticks & Human Input

1
2
3
-JOYSTICK1         Joystick (multi-axis)
-THUMBWHEEL1       Thumbwheel switch (BCD input)
-FOOT_SW1          Foot switch / foot pedal

PLC & Controller Modules

CPU & System Modules

1
2
3
4
5
6
7
8
9
10
-CPU1 .. -CPUn     PLC CPU module
-CPU_A             CPU A (primary — redundant system)
-CPU_B             CPU B (standby — redundant system)
-PM1               Power module (PLC-integrated supply)
-IM1               Interface module (rack-to-rack expansion)
-IM_SEND1          IM send module (left rack)
-IM_RECV1          IM receive module (right/remote rack)
-SYNC_MOD          Synchronisation module (redundant CPU)
-RACK1             Rack / backplane (if tagged separately)
-BM1               Backplane module

I/O Modules

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
-DI01 .. -DIn      Digital input module (numbered)
-DO01 .. -DOn      Digital output module
-AI01 .. -AIn      Analog input module (4-20mA / 0-10V)
-AO01 .. -AOn      Analog output module
-RTD01             RTD / thermocouple input module
-CNT01             Counter / high-speed input module
-ENC01             Encoder interface module
-IO_LINK01         IO-Link master module
-PWM01             PWM output module
-DI_SAFE01         Safety digital input module
-DO_SAFE01         Safety digital output module
-AI_SAFE01         Safety analog input module
-HART_MUX1         HART multiplexer module
-FF_H1_01          Foundation Fieldbus H1 card
-DP_SLAVE1         PROFIBUS DP slave module (IM for ET200)

Communications Modules

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
-CM_PN1            PROFINET communications module
-CM_PB1            PROFIBUS DP master module
-CM_DP1            PROFIBUS DP (alternative)
-CM_485_1          RS485 / Modbus RTU module
-CM_232_1          RS232 serial module
-CM_ETH1           Ethernet module (TCP/IP)
-CM_IEC104_1       IEC 60870-5-104 comms module
-CM_DNP3_1         DNP3 comms module
-CM_MQTT1          MQTT / IoT gateway module
-CM_IOLINK1        IO-Link master communications
-CM_ASI1           AS-Interface master
-CM_CAN1           CANopen master module
-CM_MODBUS1        Modbus TCP/RTU module
-NIC1              Network interface card (PC/server)
-GPS_SYNC1         GPS time synchronisation module

Safety PLC Modules

1
2
3
4
5
6
7
8
-CPU_S1            Safety CPU (SIL-rated)
-CPU_S_A           Safety CPU A (redundant)
-CPU_S_B           Safety CPU B (redundant)
-CPU_S_C           Safety CPU C (TMR)
-DI_S01            Safety DI module
-DO_S01            Safety DO module
-AI_S01            Safety AI module
-DIAG_MOD1         Diagnostic module (SIS health monitoring)

Safety Devices & Safety Relays

Safety Relays & Controllers

1
2
3
4
5
6
7
8
9
10
-F3_ESTOP          Safety relay — E-stop category (e.g. PILZ PNOZ X, Siemens 3SK)
-F3_GUARD          Safety relay — guard door monitoring
-F3_LIGHT          Safety relay — light curtain / area scanner
-F3_TWO_HAND       Safety relay — two-hand control
-F3_ENABLE         Safety relay — enabling device
-F3_MAT            Safety relay — safety mat / pressure mat
-F3_MUTE           Safety relay — muting function
-SAFE_CTRL1        Safety controller (e.g. PILZ PNOZmulti, B&R SafeLogic)
-F_SAFE_PLC        Safety PLC integrated module
-SIM1              Safety integrity monitor module

Safety Sensors & Detection

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
-SB_ESTOP          Emergency stop push button (latching, twist-to-release)
-SB_ESTOP_ROPE     Rope pull / cable pull e-stop switch
-SL_GUARD1         Guard door interlock switch (solenoid lock type)
-MAG_SAFE1         Magnetic safety switch (non-contact guard)
-TPSW1             Trapped key switch (key exchange system)
-RFID_SAFE1        RFID safety switch (coded — IEC 60947-5-3 type 4)
-LIGHT_CRT1        Light curtain (safety — Type 4 AOPD)
-AREA_SCAN1        Safety area scanner (laser — SICK, LEUZE, Keyence)
-SAFETY_MAT1       Safety pressure mat / floor mat
-SAFE_EDGE1        Safety edge / bumper (robot perimeter)
-TWO_HAND1         Two-hand control device
-ENABLE_DEV1       Enabling device (3-position switch — pendant)
-SAFE_DOOR1        Safety door interlock (EUCHNER, Schmersal)
-SAFE_HINGE1       Safety hinge switch
-INTERLOCK1        Mechanical / trapped key interlock

Communications & Network Devices

Ethernet & Industrial Network

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
-SW_CORE_OT        Core OT Ethernet switch (managed Layer 2/3)
-SW_DIST_OT1       Distribution OT switch
-SW_PN1            PROFINET switch (DIN rail — Scalance, Moxa, etc.)
-SW_EIP1           EtherNet/IP switch
-SW_MGMT1          Management network switch (out-of-band)
-SW_CORE_IT        Core IT switch
-RTR_WAN1          WAN router
-RTR_4G1           4G / LTE router (cellular)
-FW_OT_IT1         OT/IT firewall / industrial firewall
-FW_CORP1          Corporate perimeter firewall
-AP_INDUS1         Industrial WiFi access point
-FC_FIBER1         Fibre / copper media converter
-FDP1              Fibre distribution panel
-PATCH_ETH1        Ethernet patch panel
-HUB1              Network hub (legacy — avoid in new designs)

Serial & Fieldbus

1
2
3
4
5
6
7
-CM_485_1          RS485 module / repeater
-CONV_485_TCP1     RS485 to Modbus TCP converter
-DP_COUPLER1       PROFIBUS DP Y-coupler / repeater
-FF_COUPLER1       Foundation Fieldbus H1 coupler / power conditioner
-ASI_MOD1          AS-Interface module / slice
-IOLINK_HUB1       IO-Link hub
-HART_MOD1         HART modem / interface

Telemetry & WAN

1
2
3
4
5
6
7
8
9
10
11
-MODEM_4G1         4G LTE modem
-MODEM_3G1         3G UMTS modem (legacy)
-RADIO_UHF1        UHF radio modem (licensed)
-RADIO_900M1       900MHz licence-exempt radio
-SAT_MODEM1        Satellite modem (VSAT, Ku-band)
-FIBER_MOD1        Fibre optic modem
-MW_IDU1           Microwave indoor unit
-ANT_4G1           4G antenna
-ANT_RADIO1        Radio antenna (Yagi, omni)
-ANT_GPS1          GPS antenna
-LIGHTNING_ARR1    Antenna lightning arrester

Time & Synchronisation

1
2
3
4
-NTP_SRV1          GPS-disciplined NTP server
-GPS_RCV1          GPS receiver module
-PTP_GM1           IEEE 1588 PTP grandmaster clock
-TIME_CODE1        IRIG-B time code receiver (substation)

HMI, Computers & IT Hardware

HMI & Operator Terminals

1
2
3
4
5
6
7
8
9
10
11
12
13
14
-TP1               HMI touchpanel (Siemens TP, comfort series)
-TP_700            Siemens TP700 / KTP700 (by model — common)
-OP1               Operator panel (button-based, no touch)
-KTP1              Key touchpanel (combined keys + touch)
-MP1               Multi-panel HMI
-PC_HMI1           HMI PC / industrial PC with SCADA client
-PC_IPC1           Industrial PC (panel PC, DIN rail PC)
-THIN1             Thin client / zero client
-WS_HMI1           HMI workstation (office-type PC)
-WS_ENG1           Engineering workstation
-WS_SCADA1         SCADA operator workstation
-MON1 .. -MONn     Monitor / display
-TOUCH_MON1        Touchscreen monitor
-VIDEO_WALL1       Video wall processor

Servers

1
2
3
4
5
6
7
8
9
10
11
12
13
-SRV1 .. -SRVn     Server (general)
-SRV_SCADA1        SCADA primary server
-SRV_SCADA_STB     SCADA standby server
-SRV_HIST1         Historian server
-SRV_OPC1          OPC server (DA / UA)
-SRV_APP1          Application server
-SRV_ENG1          Engineering / development server
-SRV_DR1           Disaster recovery server
-SRV_WEB1          Web server
-SRV_BACKUP1       Backup server
-ESXI1             VMware ESXi host
-HYPER_V1          Microsoft Hyper-V host
-VM1 .. -VMn       Virtual machine (if tagged individually)

Storage & Peripherals

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
-NAS1              Network attached storage
-SAN1              SAN storage array
-HDD1              Hard disk drive (if tagged)
-TAPE_LIB1         Tape library
-KVM_SW1           KVM switch
-KVM_TX1           KVM extender — transmitter (server end)
-KVM_RX1           KVM extender — receiver (desk / console end)
-IPKVM1            IP KVM aggregator / console server
-SCS1              Serial console server
-USB_HUB1          USB hub
-PRINTER1          Alarm printer / label printer
-SCANNER1          Barcode scanner / document scanner
-UPS_RACK1         Rack-mount UPS
-PDU_A1            Rack PDU A side
-PDU_B1            Rack PDU B side

Cybersecurity Appliances

1
2
3
4
5
6
-DATA_DIODE1       Data diode (unidirectional security gateway)
-FW_OT_IT1         OT/IT boundary firewall appliance
-IDS_SENSOR1       OT intrusion detection sensor
-PAM_APPLN1        Privileged access management appliance
-SRV_SIEM1         SIEM server
-SRV_JUMP1         Jump server / bastion host

Heating, Cooling & Environmental

Panel Heating & Thermostat

1
2
3
4
5
-HTR1 .. -HTRn     Anti-condensation heater / panel heater
-EH1               Heating element (IEC 81346)
-THERM1            Thermostat (for panel heater control)
-HYGROSTAT1        Hygrostat (humidity-based heater control)
-PTC_HTR1          PTC self-regulating heater

Panel Cooling & Ventilation

1
2
3
4
5
6
-FAN1 .. -FANn     Panel cooling fan (filter fan unit)
-VF1               Ventilation fan (IEC 81346)
-FFU1              Filter fan unit (complete assembly)
-HEAT_EXC1         Heat exchanger / air conditioner (panel-mount)
-VORTEX1           Vortex cooler (pneumatic, Ex areas)
-AC_UNIT1          Panel air conditioning unit

Environmental Sensors

1
2
3
4
-THERM_PANEL1      Panel internal thermostat / temperature monitor
-HUMID1            Humidity sensor (internal)
-FLAME_DET1        Flame detector (cabinet fire protection)
-SMOKE_DET1        Smoke detector (inside cabinet)

Pneumatic & Hydraulic Devices

Valves

1
2
3
4
5
6
7
8
9
10
11
12
13
-YV1 .. -YVn       Solenoid valve (pneumatic / hydraulic)
-YV_FWD            Forward solenoid valve
-YV_REV            Reverse solenoid valve
-YV_CLAMP          Clamp solenoid
-YV_UNCLAMP        Unclamp solenoid
-YV_BRAKE          Brake release solenoid
-YV_VENT           Vent solenoid valve
-YV_SAFETY         Safety / dump solenoid valve
-VA_CTRL1          Motorised control valve (process)
-VA_ON_OFF1        Motorised on/off valve
-VA_ISOL1          Motorised isolation valve
-PV1               Proportional valve (hydraulic)
-SERVO_V1          Servo valve (hydraulic)

Actuators & Cylinders

1
2
3
4
5
6
7
8
-CYL1 .. -CYLn     Pneumatic / hydraulic cylinder
-CYL_EXT1          Cylinder extend solenoid
-CYL_RET1          Cylinder retract solenoid
-ACT_LIN1          Linear actuator (electric)
-ACT_ROT1          Rotary actuator
-POSITIONER1       Valve positioner (electropneumatic — 4-20mA input)
-EP_POSITIONER1    EP positioner (electro-pneumatic)
-TRANSDUCER_IP1    I/P transducer (current to pneumatic)

Pneumatic Control

1
2
3
4
-AIR_REG1          Pressure regulator (instrument air)
-FRL1              Filter-regulator-lubricator unit
-MFLD1             Pneumatic manifold
-CHECK_V1          Check valve (if monitored)

Mechanical & Structural Components

Machine Hardware (tagged when wired)

1
2
3
4
5
6
7
8
-ENC_DOOR1         Enclosure door (if interlocked)
-LOCK1             Solenoid lock (door or guard)
-LIMIT_MECH1       Mechanical limit switch (cam-operated)
-HOME_SW1          Home position switch
-BUFFER1           Mechanical buffer / end stop (if wired)
-SCALE1            Linear scale (glass or magnetic)
-RULER1            Ruler / measuring tape sensor
-LEVEL_SITE1       Spirit level sensor (machine levelling)

Cables, Conduits & Routing

IEC 81346 uses -W prefix for cables / conductors. In practice many engineers use project-specific cable numbering.

Cable Numbering Conventions

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
--- IEC 81346 style ---
-W1 .. -Wn         Cable (general)
-WC1               Control cable
-WP1               Power cable
-WS1               Signal cable (instrument)
-WF1               Fibre optic cable
-WN1               Network cable

--- Project number style (most common in practice) ---
-CAB001 .. -CABnnn Sequential cable number
-CC001             Control cable 001
-PC001             Power cable 001
-SC001             Signal cable 001
-FC001             Fibre cable 001
-NC001             Network cable 001

--- Area / route coded style ---
-CAB_A_001         Cable in area A, number 001
-CAB_MCC1_M01      Cable from MCC1 to motor M01

--- Trunkings & Conduits ---
-TRNK1             Cable trunking run 1
-CNDUIT1           Conduit run 1
-TRAY1             Cable tray run 1
-DUCT1             Underground cable duct

Panel Building Hardware

Panel Structure Components

1
2
3
4
5
6
7
8
9
10
11
12
13
-DIN1 .. -DINn     DIN rail (mounting rail)
-DUCT1 .. -DUCTn   Cable duct / wireway
-GLAND1            Cable gland (if individually tagged)
-GLAND_PG16_1      PG16 cable gland
-GLAND_M20_1       M20 metric cable gland
-GLAND_EX1         Ex-rated cable gland
-EARTH_BAR1        Earth busbar / earth rail
-PE_BAR            PE (protective earth) terminal bar
-N_BAR             Neutral terminal bar
-LOCK_OFF1         Lockout hasp / lockout device
-DOOR_LOCK1        Panel door lock
-WINDOW1           Viewing window (if referenced)
-LABEL1            Panel / device label (if in BOM)

Surge Protection

1
2
3
4
5
6
7
-SPD1 .. -SPDn     Surge protection device (SPD / lightning arrester)
-SPD_AC1           AC surge arrester (Type 1, 2, or 3)
-SPD_DC1           DC surge arrester
-SPD_DATA1         Data line surge arrester (RS485, analogue)
-SPD_ETH1          Ethernet surge arrester
-MOV1              Metal oxide varistor
-TVS1              Transient voltage suppressor

MV Switchgear Specific Devices

Devices specific to MV switchgear not covered in earlier sections

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
-QB1               Vacuum / SF6 circuit breaker
-QD1               Air-break disconnector / pantograph
-QS1               Load break switch (ring main)
-QE1 / -ES1        Earthing switch
-FU1               HRC fuse (MV TX feeder)
-CT1               Current transformer (protection / metering)
-VT1               Voltage transformer (metering / synch)
-CLOSING_COIL1     Closing coil (VCB)
-TRIP_COIL1        Trip coil 1 (VCB — main)
-TRIP_COIL2        Trip coil 2 (VCB — backup)
-ANTI_PUMP_K1      Anti-pump relay
-MOT_OP1           Motor operator (VCB / LBS motorised operation)
-POSITION_IND1     Position indicator (mechanical — open/close)
-SPRING_CHARGED1   Spring charged indicator / switch
-DRAW_OUT_LOCK1    Draw-out position interlock
-TEST_POS1         Test position switch (draw-out equipment)
-INSERT_POS1       Inserted / service position switch
-EARTH_POS1        Earthed position switch
-ARC_DETECT1       Arc flash detector (fibre / light)

Battery & DC System Devices

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
-BATT1 .. -BATTn   Battery cell / battery string
-BATT_BANK1        Battery bank (complete assembly)
-CELL_MON1         Battery cell monitoring module
-BMS1              Battery management system module
-CHRG_A            Charger A (float / boost)
-CHRG_B            Charger B (standby)
-FLOAT_CHRG1       Float charger
-BOOST_CHRG1       Boost / equalise charger
-DC_QF1            DC MCB (for DC distribution feeders)
-DC_FUSE1          DC fuse (blade or cartridge)
-DIODE1            Isolation diode (parallel charger coupling)
-SHUNT1            Current shunt (for DC current measurement)
-BATT_MON1         Battery monitor / impedance tester
-LOW_V_DISC1       Low voltage disconnect relay
-HI_V_DISC1        Overvoltage disconnect relay
-EARTH_FAULT_MON1  DC earth fault monitor (Bender, etc.)

Fire, Gas & Safety Detectors

Fire Detection

1
2
3
4
5
6
7
8
9
10
11
12
13
14
-SD1 .. -SDn       Smoke detector (general)
-SMOKE_ION1        Ionisation smoke detector
-SMOKE_OPT1        Optical smoke detector
-HEAT_DET1         Heat detector (rate-of-rise or fixed temperature)
-FLAME_IR1         IR flame detector
-FLAME_UV1         UV flame detector
-FLAME_UV_IR1      UV/IR combined flame detector
-MULTI_DET1        Multi-criteria detector (heat + smoke)
-VESDA1            VESDA / aspirating smoke detector (sampling point)
-BEAM_DET1         Beam smoke detector (projected)
-CALL_POINT1       Manual call point / break glass
-SIRN_FIRE1        Fire alarm sounder / siren
-STRB_FIRE1        Fire alarm strobe
-SOUNDER_BASE1     Detector sounder base

Gas Detection

1
2
3
4
5
6
7
8
9
10
11
12
13
-GD_GAS1           Gas detector (general)
-GD_CATA1          Catalytic bead gas detector (%LEL — combustible)
-GD_IR_FIXED1      Fixed infrared gas detector (CH4, CO2, etc.)
-GD_OP1            Open-path gas detector (IR beam — area coverage)
-GD_H2S1           H2S toxic gas detector (electrochemical)
-GD_CO1            CO toxic gas detector
-GD_O2_DEF1        Oxygen deficiency detector
-GD_O2_ENR1        Oxygen enrichment detector
-GD_CL2_1          Chlorine gas detector
-GD_NH3_1          Ammonia gas detector
-GD_SONIC1         Acoustic gas leak detector (ultrasonic)
-GD_CTRL1          Gas detection controller / addressable module
-BEACON_GAS1       Warning beacon (gas detection alarm)

Life Safety

1
2
3
4
5
6
7
8
9
-SPRINKLER1        Sprinkler flow switch (if wired to I/O)
-SUPPRS_VALVE1     Suppression system valve (FM200, CO2)
-HAND_HELD_EXT1    Portable extinguisher monitor
-PULL_STN1         Pull station (Halon / clean agent release)
-ABORT_SW1         Abort switch (suppression system)
-SOUNDER_VAC1      Evacuation sounder
-STRB_EVAC1        Evacuation strobe
-PA_SPKR1          PA / EVAC loudspeaker
-INTERCOM1         Intercom station (safety / emergency)

Building Services Devices

Access Control & Security

1
2
3
4
5
6
7
8
9
10
11
12
-CARD_RDR1         Card reader (access control)
-KEYPAD1           PIN keypad
-INTERCOM_DR1      Door intercom
-MAG_LOCK1         Magnetic door lock
-ELEC_STRIKE1      Electric door strike
-EXIT_BTN1         Exit button (green — door release)
-PIR1              PIR motion sensor (security / building)
-CCTV_CAM1         CCTV camera
-CCTV_DOM1         CCTV dome camera
-CCTV_PTZ1         CCTV PTZ camera
-VIDEO_REC1        Video recorder / NVR
-SIREN_SEC1        Security siren / intruder alarm sounder

Lighting

1
2
3
4
5
6
7
8
9
10
-EL1 .. -ELn       Luminaire / light fitting (IEC 81346)
-LIGHT1            Light fitting
-EMERG_LIGHT1      Emergency light fitting (maintained)
-EMERG_SIGN1       Emergency exit sign
-EMERG_CENTRAL1    Central battery emergency lighting system
-DALI_CTRL1        DALI lighting controller
-DALI_BUS1         DALI bus coupler / power supply
-DIM1              Dimmer module
-SENS_LIGHT1       Daylight sensor / photocell
-MOTION_LIGHT1     Motion-activated lighting switch

Numbering Conventions & Suffixes

Sequential Numbering (most common)

1
2
3
4
-K1, -K2, -K3, -K4       Simple sequential — good for small panels
-KM1, -KM2, -KM3         Sequential by type — good for MCCs
-DI01, -DI02, -DI03      Zero-padded — essential for sorted reports
-FT101, -FT102, -FT103   ISA loop-based — process industry

Alphabetical Suffixes (for duplicates / phases)

1
2
3
4
-CT_A, -CT_B, -CT_C      Phase A, B, C CTs
-CPU_A, -CPU_B            Redundant pair A/B
-PS_A, -PS_B              Redundant power supplies
-QF_INC_A, -QF_INC_B     Dual incomer A and B

Descriptive Suffixes (for clarity in complex panels)

1
2
3
4
5
6
-KM_MAIN               Immediately identifies main contactor
-KM_STAR               Identifies star contactor clearly
-F_OC_A                Overcurrent relay incomer A
-HL_RUN                Run indicator (no ambiguity)
-SB_ESTOP              E-stop button (safety critical — must be obvious)
-SW_PN_A1              Switch for PROFINET in area A1

ISA Loop Number Convention

1
2
3
4
5
6
7
8
-FT101     First two letters = variable + device type, three digits = loop number
-FT101A    Suffix letter = multiple devices in same loop (transmitter A)
-FT101B    Second transmitter in same loop (e.g. 2oo3 voting)
-FT101C    Third transmitter in loop (TMR / 2oo3)
-LS401H    Level switch high (H suffix = high trip)
-LS401L    Level switch low (L suffix = low trip)
-LS401HH   Level switch high-high (HH = safety trip)
-LS401LL   Level switch low-low (LL = safety trip)

Panel / Location Coded Prefixes (alternative style)

1
2
-CP1_K1    Relay in panel CP1 — location embedded in device tag
           (Not recommended in EPLAN — this is what the + location is for)

Full Tag Examples — Complete Projects

Example 1 — DOL Motor Starter in MCC

1
2
3
4
5
6
7
8
9
10
11
12
13
=PWR.INC+MCC1.INC-QF_INC                Main incomer MCCB
=METER+MCC1.INC-CT_INC                  Incomer CT
=METER+MCC1.INC-PQ1                     Power analyser
=MOTOR.DOL+MCC1.M01-QF1                 Motor M01 feeder MCCB
=MOTOR.DOL+MCC1.M01-F_MOTOR1            Motor protection relay
=MOTOR.DOL+MCC1.M01-KM_MAIN             Main contactor
=CTRL+MCC1.M01-SS_LOCAL                 Local/remote selector
=CTRL+MCC1.M01-SB_START                 Start push button
=CTRL+MCC1.M01-SB_STOP                  Stop push button
=CTRL+MCC1.M01-HL_RUN                   Run indicator lamp
=CTRL+MCC1.M01-HL_TRIP                  Trip indicator lamp
=CTRL+MCC1.M01-X1                       Terminal block (field wiring)
=MOTOR+FIELD-M1                         Motor (in field)

Example 2 — Star-Delta Starter

1
2
3
4
5
6
7
8
9
10
11
12
=MOTOR.STAR_D+MCC1.M02-QF1             Feeder MCCB
=MOTOR.STAR_D+MCC1.M02-F_MOTOR2        Motor protection relay
=MOTOR.STAR_D+MCC1.M02-KM_MAIN         Line contactor
=MOTOR.STAR_D+MCC1.M02-KM_STAR         Star contactor
=MOTOR.STAR_D+MCC1.M02-KM_DELTA        Delta contactor
=MOTOR.STAR_D+MCC1.M02-KT_SD           Star-delta timer
=CTRL+MCC1.M02-SB_START                Start button
=CTRL+MCC1.M02-SB_STOP                 Stop button
=CTRL+MCC1.M02-HL_STAR                 Star mode indicator
=CTRL+MCC1.M02-HL_DELTA                Delta mode indicator
=CTRL+MCC1.M02-HL_TRIP                 Trip indicator
=MOTOR+FIELD-M2                        Motor (in field)

Example 3 — PLC Control Panel

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
=PWR.CTRL+CP1.POWER-QF_MAINS           Mains incoming MCB
=PWR.24V+CP1.POWER-PS1                 24VDC SMPS primary
=PWR.24V+CP1.POWER-PS2                 24VDC SMPS redundant
=PWR.UPS+CP1.POWER-UPS_BUF1            24VDC UPS buffer module
=PWR.24V+CP1.DIST_24V-FT1              PLC fused terminal block
=PWR.24V+CP1.DIST_24V-FT2              I/O fused terminal block
=PWR.24V+CP1.DIST_24V-FT3              Field sensor fused terminal
=CTRL.PLC+CP1.PLC-CPU1                 PLC CPU
=CTRL.IO+CP1.IO-DI01                   Digital input module 01
=CTRL.IO+CP1.IO-DO01                   Digital output module 01
=CTRL.IO+CP1.IO-AI01                   Analog input module 01
=CTRL.COMM+CP1.COMM-CM_PN1             PROFINET module
=CTRL.SAFE+CP1.SAFE-F3_ESTOP           E-stop safety relay
=CTRL.SAFE+CP1.SAFE-F3_GUARD           Guard door safety relay
=CTRL+CP1.RELAY-K_WD                   Watchdog relay
=CTRL.HMI+CP1.DOOR.HMI-TP_700         HMI touchpanel
=SAFE.ESTOP+CP1.DOOR.OP-SB_ESTOP       E-stop push button
=CTRL+CP1.DOOR.OP-SS_MODE              Mode selector
=CTRL+CP1.DOOR.OP-SB_RESET             Reset button
=CTRL+CP1.DOOR.OP-HL_POWER            Power indicator
=CTRL+CP1.DOOR.OP-HL_RUN              Run indicator
=CTRL+CP1.DOOR.OP-HL_FAULT            Fault indicator
=CTRL+CP1.TERM.DI-X_DI1               DI terminal block
=CTRL+CP1.TERM.AI-X_AI1               AI terminal block
=CTRL+CP1.TERM.SAFE-X_SAFE1           Safety terminal block

Example 4 — Process Instrumentation Loop (Flow)

1
2
3
4
5
6
7
=INST+FIELD-FE101                      Flow element (orifice plate)
=INST+FIELD-FT101                      Flow transmitter (HART 4-20mA)
=INST+INST_CAB_01.BARRIER.AI-Z_FT101   Zener barrier for FT101
=INST+MARSH_CAB_A.AI-X_AI_FT101       Marshalling terminal block
=DCS.IO+DCS_CAB1.IO_RACK_A-AI01       DCS AI card (receives FT101 signal)
=DCS+CTRL_RM.DESK1.PC_HMI1-WS_DCS1   DCS HMI workstation
=PWR+MCC1.M01-KM_MAIN                 Pump contactor (flow control output)

Example 5 — MV Switchgear Feeder Panel

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
=MV.FDR+MV_SW1.FDR_1-QB1              Feeder VCB
=MV.FDR+MV_SW1.FDR_1-QD1             Line disconnector
=MV.FDR+MV_SW1.FDR_1-QE1             Earth switch
=MV.FDR+MV_SW1.FDR_1-CT1             Protection CT phase A
=MV.FDR+MV_SW1.FDR_1-CT2             Protection CT phase B
=MV.FDR+MV_SW1.FDR_1-CT3             Protection CT phase C
=PROT.OC+MV_SW1.FDR_1-F_OC1          Overcurrent relay (e.g. REF615, SEL-751)
=PROT.EF+MV_SW1.FDR_1-F_EF1          Earth fault relay
=METER+MV_SW1.FDR_1-PQ1              Power quality analyser
=CTRL+MV_SW1.FDR_1-CLOSING_COIL1     VCB closing coil
=CTRL+MV_SW1.FDR_1-TRIP_COIL1        VCB trip coil 1
=CTRL+MV_SW1.FDR_1-TRIP_COIL2        VCB trip coil 2 (backup)
=CTRL+MV_SW1.FDR_1-ANTI_PUMP_K1      Anti-pump relay
=CTRL+MV_SW1.FDR_1-HL_CLOSED         Breaker closed indicator (red)
=CTRL+MV_SW1.FDR_1-HL_OPEN           Breaker open indicator (green)
=CTRL+MV_SW1.FDR_1-SB_CLOSE          Close push button
=CTRL+MV_SW1.FDR_1-SB_OPEN           Open push button
=CTRL+MV_SW1.FDR_1-SS_LOCAL          Local/remote selector
=CTRL+MV_SW1.FDR_1-X1                Control wiring terminal strip
=DC+MV_SW1.FDR_1-QF_DC1              DC MCB for trip circuit

Example 6 — Safety PLC SIL2 Shutdown Loop

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
--- Field sensing ---
=SIS.IO+FIELD-PT201A                  Pressure transmitter A (SIL2 — 2oo3)
=SIS.IO+FIELD-PT201B                  Pressure transmitter B
=SIS.IO+FIELD-PT201C                  Pressure transmitter C

--- Marshalling ---
=SIS.IO+MARSH_CAB_B.DI_SAFE-X_PT201  Safety PT terminal (2oo3 wiring)
=SIS.IO+MARSH_CAB_B.BARRIER_S-Z_PT201A  Safety barrier for PT201A

--- SIS Logic Solver ---
=SIS.IO+SIS_CAB1.IO_A-DI_S01_A       Safety DI module (1oo2D architecture)
=SIS.IO+SIS_CAB1.IO_B-DI_S01_B       Safety DI module B
=SIS.LOGIC+SIS_CAB1.LOGIC_A-CPU_S_A  SIS logic solver A
=SIS.LOGIC+SIS_CAB1.LOGIC_B-CPU_S_B  SIS logic solver B
=SIS.POWER+SIS_CAB1.POWER_A-PS_S_A   SIS power supply A
=SIS.POWER+SIS_CAB1.POWER_B-PS_S_B   SIS power supply B

--- Final Element ---
=SIS.IO+SIS_CAB1.IO_A-DO_S01_A       Safety DO module A
=ESD.L2+FIELD-SDV201                  Shutdown valve (solenoid — de-energise to close)
=ESD.L2+FIELD-YV_SDV201              Solenoid valve coil on SDV201
=ESD.L2+FIELD-ZS_SDV201_O            Position switch — open
=ESD.L2+FIELD-ZS_SDV201_C            Position switch — closed

Cross-Reference: IEC 81346 vs ISA-5.1 vs Common Practice

DeviceIEC 81346ISA-5.1Common Practice
Circuit breaker (LV)QFQF, CB, MCB, MCCB
Circuit breaker (MV)QBQB, VCB, ACB
ContactorKC / KMKM, K
FuseFAFU, F, FA
MotorMAM, MA
Solenoid valveYV / YAYV, SV, VA
Relay (aux)KAK, KA, CR
TimerKTKT, TR, T
Indicator lampHLHL, PL, IL
Push buttonSBSB, PB, BS
Selector switchSS / SASS, CS, SA
TransformerTM / TT, TR, TM
CTTACT, TA
VTTVVT, PT, TV
Power supplyGSPS, GS, PSU
UPSGUUPS, GU
Terminal blockXT / XX, XT, TB
Flow transmitterBFFTFT (process), BF (IEC)
Pressure transmitterBPPTPT (process), BP (IEC)
Temperature transmitterBTTTTT (process), BT (IEC)
Level transmitterBLLTLT (process), BL (IEC)
Control valveVACV / FCVFCV, PCV, LCV (ISA)
VFDNAVFD, VSD, NA
Safety relayKFF3, KF, SR
Zener barrierZAZA, ZB, MTL
EncoderBKENC, BK, EC

Common Mistakes

❌ Wrong✅ CorrectReason
-PANEL_A+PANEL_APanel is a location, not a device
-CONTROL_SYSTEM=CTRLControl system is a function, not a device
-M_01 (inconsistent spacing)-M01Spaces / inconsistency breaks EPLAN sort order
-K1, -k1, -K_1 for same relay typePick one style — -K1Inconsistent capitalisation and separators = different devices
-FT101 without context=INST+FIELD-FT101Always needs = and + to be complete
Using name only: -MAIN_CONTACTOR-KM_MAINNo type letter = can’t filter by device type in reports
Same tag in two locations: +CP1-K1 and +MCC1-K1Both valid if function differsDuplicate tags across different =+ combinations are OK — EPLAN uses full path
-1K (number before letter)-K1IEC 81346 requires letter code first
-QF001 and -QF01 in same project-QF01 throughoutMixed zero-padding breaks alphabetical sort in reports
-PT_HIGH_PRESSURE_TRANSMITTER_LOOP_201-PT201Too long — truncated in reports, hard to read on diagrams
Omitting device tag entirelyAlways assign - tagBlank device tag = invisible in BOM and terminal reports
Using -WIRE1 for every wireReserve -W for cables, not individual wiresEPLAN handles internal wiring differently from cables

Expert Tips

1. Always use a letter code — never just a number

-K1 not -1. The letter is what lets EPLAN and IEC reports group, filter, and sort by device type. Reports like parts lists, terminal diagrams, and cable schedules all depend on it.

2. Zero-pad your numbers from the start

-DI01 not -DI1. When you have -DI01 through -DI12, they sort correctly. -DI1 through -DI12 sorts as 1, 10, 11, 12, 2, 3… which makes every report painful.

3. Choose IEC 81346 codes OR ISA codes — not both

Process plant? Use ISA (-FT101, -PT201). Machine or panel? Use IEC (-KM1, -QF1). The worst projects mix both. Decide at project kick-off.

4. Descriptive suffixes add value in complex panels

-KM_MAIN, -KM_STAR, -KM_DELTA is better than -KM1, -KM2, -KM3 in a star-delta starter. The person wiring the cabinet shouldn’t need to look up which -KM2 is.

5. ISA loop numbers carry meaning — use them consistently

-FT101 means flow transmitter, loop 101. The loop number should match your P&ID. Don’t start loops at 1 — use area-coded numbers (100-series = area 1, 200-series = area 2) for large plants.

6. Use letter suffixes for redundant devices in the same loop

-FT101A, -FT101B, -FT101C for three transmitters in a 2oo3 SIL voting loop. This is the ISA convention and immediately tells the instrument engineer the devices belong to the same loop.

7. High-high / low-low convention for safety trips

-LSH401 = level switch high, -LSHH401 = level switch high-high (safety). The H/L/HH/LL suffixes are recognised across industries. Use them for anything connected to an SIS/ESD.

8. Terminal blocks get -X1, -X2 etc. — not -T1 or -TB1

EPLAN specifically uses -X prefix for terminal blocks in its terminal diagram generation engine. Using other letters means your terminal reports may not auto-populate correctly.

9. Never embed location into the device tag

-CP1_K1 is wrong — the panel CP1 information belongs in +CP1. The device tag should just be -K1. The full reference =CTRL+CP1-K1 already carries the location.

10. Document your device tag convention in a legend page

Create a EAC (explanatory documents) page at the front of the project listing all device tag abbreviations used. Future engineers, clients, and maintenance teams will spend hours less confused.


Based on IEC 81346 | IEC 61346 | ISA-5.1 | ISA-20 | IEC 60617 | IEC 61131 | IEC 61511 | IEC 62271 | IEC 61439 | IEC 61850 Expert conventions compiled from electrical, automation, instrumentation, process, power, safety, and IT engineering disciplines